
EX-6120, 6165 SERIES IR
ENMET Corporation
4
Important
Connect enclosure
earth-ground to a high
integrity earth ground
ATEX certified Ex d armoured
cable glands
- +
PSU
- +
Aout
0V
Rx
Tx
RS232
Conduit
or Shielded Cable
Conduit
or Armoured Cable
Mount vertically
as shown
Relay 1
Relay 2
Relay 3
3.2 Wiring the EX-6120, 6165 S
ERIES
IR to a Control Unit
C
AUTION
:
Area must be declassified during installation.
If the EX-6120, 6165 S
ERIES
IR is installed in a hazardous location as defined by the National Electrical Code, then
ALL wiring must be in accordance with the National code and any local governing codes.
Open the enclosure, and remove the 2 screws that retain the display overlay to the circuit board.
Turn cover securing stud counter-clockwise to allow cover to open.
Remove cover by rotating counter-clockwise.
Figure3: Access to EX-6120, 6165 S
ERIES
IR for Connection to a Control Unit
The cable entry threads are 20mm, ½” or ¾” NPT female.
The EX-6120, 6165 S
ERIES
IR enclosure is manufactured from die cast aluminum*. Therefore, the use of glands,
conduit fittings and blanks made from brass should be avoided because if moisture is present, bi-metallic corrosion may
occur due to the chemical reaction between the two materials.
Glands and fittings plated with nickel, tin or zinc will provide improved protection but in harsh environments the use of
stainless steel is recommended.
Figure 4: Armored Cable Gland Installation
Relays - three relays are provided:
Alarm 1 and Alarm 2 are associated with the alarm points.
Alarm 3 is associated with fault conditions.
All relays are factory set to de-energize state non alarm.
Komentarze do niniejszej Instrukcji